While we often speak of electricity supply in terms of raw power inputs and demand – whether from gigawatt-scale nuclear plants, the terawatt hours of annual demand in each U.S. state, or even individual 15 W light bulbs – there is another dimension that is less discussed but no less critical: frequency.
The three main U.S. grids run on a frequency of 60 cycles per second (60 hertz), and European grids on 50 Hz. Any significant deviation from this would wreck electrical equipment, including the appliances of end users, and as a result relays are set to trip if the grid exceeds a relatively narrow band of acceptable frequencies.
These frequencies can rise or fall if there is an imbalance between the supply of power and end user demand. When this happens, the enormous spinning bulk of turbines at hydro, gas, coal, oil, or nuclear plants can help address the problem until more resources are brought online.
This entire system is under threat, as large generators are going offline and being replaced by wind, solar, and batteries which have no large spinning masses. While wind can supply “synthetic inertia” to compensate, this is not the same, and eventually a whole new system will need to be created if we are to transition entire grids to renewable energy resources.
Frequency control
While keeping the frequency of the grid within a narrow range is one of the central tasks of maintaining power supply, the bulk power system typically doesn’t wander out of standard frequency on its own. Deviation usually occurs when there is a mismatch between supply and demand – like when a large generator goes offline.
A common misunderstanding about frequency control is the idea that large spinning masses keep the power grid at a stable frequency during times of imbalance between supply and demand. “Inertia only sets the initial rate at which the frequency falls – it buys you time,” notes Mark Ahlstrom, an engineer who works with the Energy Systems Integration Group (ESIG). He notes that ultimately, frequencies will not stabilize until the supply and demand balance is corrected.
In the 20th century, this was the system for frequency stabilization. The grid was comprised solely of large generators with heavy steam and hydroelectric turbines, and in early years motors connected to the grid provided additional inertia. But the 21st century grid is different. Notably, these large spinning masses are being replaced with wind and solar power plants that do not have the same characteristics: For solar there is no spinning mass at all.
This does not mean that inverters are not capable of frequency control. In fact, they can react much faster than the primary frequency response which is currently deployed. “They are about as fast as you can get,” explains Ahlstrom. In fact, if needed, inverters can respond so quickly to restore frequency that the initial supply-demand imbalance could go undetected, causing other problems.
This danger – that inverters could respond too quickly – underscores the difference between perception and actual needs regarding frequency control. In the current system, frequency deviations serve as a necessary warning that supply and demand are imbalanced.
FERC freak out
In the United States, regulators have observed the retirement of conventional generation and its replacement with wind and solar; and have been concerned about insufficient inertia. In 2009, the Federal Energy Regulatory Commission (FERC) began a process that culminated last February in Order 842, which requires both large and small power plants to “install, maintain, and operate equipment capable of providing primary frequency response (PFR) as a condition of interconnection” in order to “address the potential reliability impact of the evolving generation resource mix.”
In their 2016 comments, Sierra Club and the Sustainable FERC Project argued that there is adequate PFR in all interconnections, and that over the longer term FERC should “explore measures other than mandates” to ensure compliance with reliability standards – including encouraging “procurement of fast-acting demand response from storage and other demand-side resources.”
Experts who pv magazine spoke with for this article have also suggested that this may be an overreaction on FERC’s part. “In the Eastern and Western Interconnections, there probably isn’t a problem for the next couple of decades,” notes ESIG’s Ahlstrom.
However, in the Electric Reliability Council of Texas (ERCOT) grid, things may be different. Wind represented 19% of the electricity generated in ERCOT last year, and wind output has already peaked at more than half of instantaneous demand. As a result, some of the biggest concerns about the loss of inertia and frequency control have come from ERCOT.
But even in the Eastern and Western Interconnections, if more ambitious transitions to renewable energy are realized – such as U.S. Representative Alexandria Ocasio-Cortez’s call for 100% renewable energy by 2030 – these problems will have to be grappled with.
Grid-following, or grid-forming?
Wind plants have the ability to supply what has been called “synthetic inertia” by essentially overdriving to give a little more oomph. However, multiple experts express disdain for this term, noting that what wind turbines supply is not inertia, but extra power. This doesn’t correct frequency as much as it alleviates a portion of the imbalance which caused the frequency deviation in the first place.
Inverters can be programmed to help to control frequency as well, and the way that PV plants are operated can be a factor in the ability to provide frequency response. “If you were going to provide fast frequency response from PV plants, you would have to be running in a partially curtailed state,” explains Ahlstrom.
Additionally, storage devices can provide frequency support and balance supply and demand, and these can be available at times when solar and wind are not.
But a bigger question is whether it is best to use inverters this way. With inverters, we aren’t stuck with the characteristics of large spinning masses, and have more options to provide system stability.
Broadly speaking, there are two main ways to use inverters for frequency control: grid-following or grid-forming. Grid-following inverters measure the grid voltage and frequency, and inject the correct real and reactive power. Grid-forming inverters create a local voltage and frequency, and then try to move that voltage to cause the correct real and reactive power to flow into the system.
Systems based on grid-forming inverters are in operation on microgrids around the world, but have not been implemented at the scale needed for the USA to run on wind, solar, and batteries. “To the best of the authors’ knowledge, there is no practical example of parallel grid-forming inverters in a large power system under various penetration levels of inverter-based generation,” note Julia Matevosyan and Fred Huang of ERCOT in a paper published earlier this year. Another problem is that grid-forming inverters are currently only made for small generators. “There also is currently no commercially available grid-forming inverter for a large-scale power system application,” warn Matevosyan and Huang.
This does not mean it is impossible. But it does introduce a number of uncertainties. “In practice, the question is: Is the right kind of software being deployed, is the right headroom available, and will thousands of these devices behave the way we need them to?” asks Eric Gimon, a senior fellow at Energy Innovation.
Troubles of the transition
While it is unclear how a large grid serving millions of customers based on grid-forming inverters will function, it may be messier to transition from frequency regulation based on inertia to a grid in which supply/demand balance and frequency regulation run under a new paradigm.
Matevosyan and Huang of ERCOT note that the mechanics of a transition mean deploying grid-forming inverters under the current paradigm. “If grid-forming technologies are to be a viable solution, they will have to operate reliably in parallel with synchronous generation during the extended transition period.”
And if we move to very high levels of renewable energy, but delay the transition to a new frequency control paradigm, problems will be more severe, as the frequency could swing wildly when conventional power plants go offline.
New solutions
In early December, PXiSE Energy announced a contract to supply a distributed energy resource management solution (DERMS) for a public utility in Western Australia, which will manage 50,000 distributed energy resources including rooftop PV systems and batteries across 2.3 million square kilometers.
This is the largest scale a DERMS solution has ever been implemented at. PXiSE’s ACT Platform will control the output of tens of thousands of DERMS, adjusting supply to meet demand, with a high degree of accuracy enabled by information collected by a network of synchrophasors. “DERMS can make the adjustment as fast as a few seconds,” PXiSE President Patrick Lee explains. “We have added functions to control frequency in the sub-second range.”
Solutions like ACT work very differently than the previous paradigm of a central point of control. “Instead of managing a large grid with a single heartbeat, the deployment in Australia would be breaking down those large grids into smaller grids,” notes Lee. “You can do your energy exchange across those smaller grids.”
This solution has raw technical advantages over the existing system of distant spinning masses. “Reliability means that you must be able to quickly adjust to a dynamic condition,” explains Lee. “You need to have speed and accuracy. If you look at traditional technology, speed and accuracy are not things that you have.”
Lee notes that the PXiSE solution has been built to enable the transition to non frequency-based control, so that grid operators don’t have to adopt one system and replace it when they switch over to an inverter-based control paradigm.
Lee says that the transition to intelligent electronic control like his company’s solution will not necessarily be easy, but more for reasons of human inertia. “People will want to hang on to the way we have been controlling the grid for the last 100+ years,” observes Lee. “It is not just the regulator or the system operator, but also the supplier.” But he also notes that “there will be a point where you cannot hang on much longer.”
This content is protected by copyright and may not be reused. If you want to cooperate with us and would like to reuse some of our content, please contact: editors@pv-magazine.com.
Great story and timely topic. The grid is here to serve humanity and it like all human inventions must change. There is not future in the past, as many wise people have said. A grid made up of many smaller DER facilities is the future, there’s no question about that for the foreseeable future. Remember, DER in the US is almost 30 percent more expensive in the US than in Australia and Germany because they have effectively brought down the soft costs like permitting. Everyone in the power industry must do their part to help make the transition to a better (more reliable, resilient, sustainable) grid so we can have sustainable power for all of society. Let’s do it!
Very interesting article. Power engineering is opaque to many of us who want to work to replace fossile fuels. We hear claims about grid reliability being sacrificed, but we don’t know enough to evaluate those claims. This is a nice introduction to frequency control.
This quote in particular stood out for me:
“If grid-forming technologies are to be a viable solution, they will have to operate reliably in parallel with synchronous generation during the extended transition period.”
We are transforming an energy system here, and doing it while still depending on the old system. Like trying to live in a house you are remodeling. The engineers have their work cut out for them.
Excelent information
There are two high voltage AC to DC converters back-to-back at the dam on the river between Brazil and Paraguay. They are used to convert between 50 and 60 Hz. These and others like them have been supplying gigawatts of power for decades and isolate that ‘rotating mass’ from the grid. So this type of supply with its frequency unregulated is not new.
It seems to me that ‘the grid’ is depending on leading or lagging phase to supply power instead of increasing or lowering the voltage. Does the ‘new paradigm’ mean that the grid will have to transition from stable voltage but variable frequency to stable frequency but variable voltage? Not enough information, I guess.
The discussion in this article is in the right direction but with not enough understanding of the topic. First of all, it is wrong to talk about inertia of the system, it should be the energy stored in the system, not even kinetic energy necessarily. For example, two asynchronous generators with the same inertia but one with 4 poles and one with two poles have the ratio of stored kinetic energy of 1:4. Secondly, if the system has only inverter based sources, where is the frequency deviation going
to come from? In this case the best thing we can do is to look at the problem as a transient problem. With a system with
synchronous generation, frequency deviation is an indication of supply/demand imbalance and is used as the feedback signal
for primary frequency control, in a purely inverter based system, there is no such feedback signal. Can the voltage take over
such a role? Maybe, but as we know, there is weak coupling between the voltage and real power. I would also like to
mention that back to back HVDC to connect 50Hz-60Hz systems is not the best solution. IMHO, a pair of synchronous
machines would be a better solution. If the goal is to “isolate that ‘rotating mass’ from the grid”, which should be for smaller
frequency differences, a variable frequency transformer is definitely a better solution unless we are talking interconnection size grid.